Lyte DIN Rail Power Supply HIKVISION DRL-48V75W1AZ

Mô tả

Lyte DIN Rail Power Supply HIKVISION DRL-48V75W1AZ

– Input Voltage Range: 85-264Vac.

– Rated Output Voltage: 48Vdc.

– Rated Output Current: 1.57A.

– Universal AC input voltage range.

– Built-in constant current circuit for reactive loads.

– Up to 90% efficiency.

– Full power from -10°C to +50°C @ 230Vac with -30°C Cold Start.

– Compliance to SEMI F47 @ 200Vac.

– NEC Class 2/Limited Power Source (LPS) certified.

Thông số kỹ thuật

Input Ratings/Characteristics
Nominal Input Voltage 100-240Vac
Input Voltage Range 85-264Vac
Nominal Input Frequency 50-60Hz
Input Frequency Range 47-63Hz
Input Current 1.4A typ. @ 115Vac, 0.9A typ. @ 230Vac
Efficiency at 100% Load 90% typ. @ 230Vac
Max Inrush Current (Cold Start) 50A typ. @ 230Vac
Leakage Current < 1mA @ 240Vac
Output Ratings / Characteristics
Nominal Output Voltage 48Vdc
Factory Set Point Tolerance 48Vdc ± 1%
Output Voltage Adjustment Range 43.2-52.8Vdc
Output Current 1.57A
Output Power 75.36W
Line Regulation < 0.5% (@ 85-264Vac, 100% load)
Load Regulation < 1% (0-100% load)
PARD (20MHz) < 240mVpp @ > -10°C to +70°C
< 480mVpp @ ≤ -10°C to -30°C
Rise Time 30ms typ. @ nominal input (100% load)
Start-up Time 1200ms typ. @ 115Vac (100% load)
1000ms typ. @ 230Vac (100% load)
Hold-up Time 16ms typ. @ 115Vac (100% load)
60ms typ. @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 10% @ 115Vac & 230Vac input, 0-50%, 50-100% load
(Slew Rate: 2.5A/μS, 50% duty cycle @ 100Hz & 1KHz)
Start-up with Capacitive Loads 4,000µF Max
Mechanical
Case Cover / Chassis Plastic
Dimensions (L x W x D) 123.6 x 27 x 102 mm
Unit Weight 0.22 kg
Indicator Green LED (DC OK)
Cooling System Convection
Terminal Input: 3 Pins (Rated 300V/16A)
Output: 4 Pins (Rated 300V/16A)
Wire Input: AWG 18-12
Output: AWG 22-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
Noise (1 Meter from power supply) Sound Pressure Level (SPL) < 25dBA
Environment
Surrounding Air Temperature Operating: -20°C to +70°C (-30°C Cold Start)
Storage: -40°C to +85°C
Power De-rating Temperature:
-10°C to -20°C de-rate power by 1% / °C
> 40°C de-rate power by 1.67% / °C @ 115Vac
> 50°C de-rate power by 2.5% / °C @ 230Vac
Input Voltage:  < 100Vac de-rate power by 1.33% / Vac
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 5,000 Meters (16,400 ft.)
Shock Test Non-Operating: IEC 60068-2-27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total
Operating: IEC 60068-2-27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis
Vibration Non-Operating: IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions
Operating: IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s²
(2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for X direction
Over Voltage Category II
Pollution Degree 2
Protections
Overvoltage <62.4V, SELV Output, Latch Mode
Overload / Overcurrent 105 – 133% of rated load current, Constant current limit, Auto-recovery
Over Temperature Latch Mode
Short Circuit Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Internal Fuse at L pin F5AH
Degree of Protection IP20
Protection Against Shock Class I with PE connection